Alarm System Control Panel
Fire alarm control panels designed to comply with EN54 Parts 2 & 4 and suitable for installations meeting BS5839 Part 1.
Easy to install, with clear fire/fault indication
Programmable with option for zone and sounder configurations
Integral PSU and battery support for up to 8 alarms sounder circuits, 2 auxiliary relay contacts and zone disable facility
Suitable for automatic detectors, manual call points, or a combination of both
Includes an external evacuation facility
Detectors and manual call points can be wired in any order
Detector removal monitoring via diode base
Auto reset function and silent maintenance tests configured by each individual zone
Any zone can be selected for special fire activities, zones may be disabled at any time
Keypad access with password protection
Batteries provide 72 hour standby
Detection circuits
24 (max) per zone @ 16V (min quiescent)
20mA @ 7V across trigger devices
27mA @ 0V fire voltage
Alarm circuits
2 per panel (min), 8 on 8 Zone panel
1A (max) load on 1&2 Zone panels
1·5A (max) load on 4&8 Zone panels
Auxilary relay contacts
1 set N/O and 1 set N/C, rated 1A @ 24Vdc
Class Change
1 pair N/O un-monitored terminals operated via external remote
Fault Monitoring
Zones;
Open/Short circuit via end-of-line
capacitor and polarising diode
Alarm Circuits:
Open/Short circuit with 22kΩ
end-of-line resistor
Other;
Earth/Fault, battery charger, mains
power and fuse state
Controls
Sound Alarms, Silence Alarms, Reset, Cancel
Fault Buzzer, Lamp Test, Disable Zone
Batteries (not supplied)
1&2 Zone (2x12V 2Ah
597-813
)
4&8 Zone (2x12V 2.8Ah
597-829
)
Gent
Smoke and Heat Detectors
Providing a comprehensive range of sensing devices for use on DC monitored, automatic fire detection systems, this series of smoke and sensing devices has been designed to provide easy installation and maintenance with full detector interchangeability. Particular emphasis has been given to the overall series des...